HomeMy WebLinkAboutgl_waterheater-archiveGUIDELINES FOR SIZING WATER HEATERSCalifornia Conference of Directors of Environmental Health
September, 1995
I.BACKGROUNDA critical factor in preventing foodborne illnesses in a food facility is the provision of an
adequate supply of hot water for the washing of hands, utensils, equipment, and the facility
itself. The installation of a properly sized water heater will ensure that a sufficient amount of
hot water will be available at all times.II.PURPOSEThe purpose of these guidelines is to provide a set of criteria that will assist architects,
designers, contractors and owners in properly sizing water heaters to adequately meet the
anticipated hot water demands of food facilities in California.
Food facilities with water heaters sized according to these criteria should be capable of
complying with the requirements for providing an adequate hot water supply as required by
the California Uniform Retail Food Facilities Law.III.LEGAL AUTHORITYCalifornia Health and Safety Code, Chapter 4, Article 8, Sections 27623, 27624, 27625,
27627, and 27627.3.IV.DEFINITIONS•Booster Heater: An instantaneous water heater designed and intended to raise the
temperature of hot water to a higher temperature for a specific purpose, such as for the
sanitizing rinse on a high temperature automatic dishmachine.
•BTU (British Thermal Unit): The quantity of heat required to raise the temperature of
one pound of water one degree Fahrenheit.
•GPH (Gallons Per Hour): The amount of water, in gallons, that is used each hour by
the plumbing fixtures and equipment, such as dishmachines.
•GPM (Gallons Per Minute): The amount of water, in gallons, flowing through a
plumbing fixture or through an instantaneous water heater per minute.•Instantaneous Water Heater: A water heater that generates hot water on demand.
•KW (Kilowatt): A unit of electric power equal to 1,000 watts.
•Rise: The temperature of water as it leaves the water heater minus the temperature of
the water entering the water heater.
•Storage Water Heater: A water heater that incorporates a thermostat, a storage tank,
and a burner or heating elements, to heat and maintain the water within the tank at a
specific temperature.
•Thermal Efficiency: The measure of the overall efficiency of the water heater, taking
Water Heater Guidelines
Page 2 of 6
into consideration loss of energy due to combustion, radiation, convection and
conduction of heat from the unit.V.GENERAL REQUIREMENTSA.A water heater shall be provided which is capable of generating an adequate supply of
hot water, at a temperature of at least 120° Fahrenheit, to all sinks, janitorial facilities,
and other equipment and fixtures that use hot water, at all times.
B.Water heaters and their installation must be in compliance with all local building code
requirements.
C.Water heaters that use reclaimed heat from equipment to heat water must be evaluated
on a case by case basis.VI.SIZING REQUIREMENTS FOR STORAGE WATER HEATERSA.For food facilities that utilize multiservice eating and drinking utensils, the water heater
shall have a recovery rate equal to or greater than 100% of the computed hourly hot
water demand, in gallons per hour (GPH).
B.For food facilities that use only single-service eating and drinking utensils, or don't use
utensils at all, the water heater shall have a recovery rate equal to or greater than 80%
of the computed hourly hot water demand, in GPH.
C.For food facilities that handle and sell only prepackaged foods, a water heater with a
minimum storage capacity of ten gallons must be provided.
D.The hourly hot water demand for the food facility, in GPH, is calculated by adding
together the estimated hot water demands for all sinks and other equipment, such as
dishmachines, which utilize hot water. The estimated hot water demands for sinks and
other equipment that utilize hot water are listed in Appendix I. The hot water demands
for automatic warewashers, such as dishmachines, glasswashers, and potwashers are
found in NSF International listings or listings established by other nationally recognized
testing laboratories.
E.The following examples are provided to explain how to calculate the total hourly hot
water demand:
1.Food facility that utilizes only single service eating and drinking utensils:
Assume:
1 18" X 18" three compartment sink 42 GPH
2 hand lavatories 10 GPH (5 GPH each)
1 janitorial sink 15 GPH
67 GPH total hourly hot water demand
67 GPH X 80% allowance for single service utensils = 54 GPH
For the food facility in this example, a water heater would be required which will
recover 54 GPH.
Water Heater Guidelines
Page 3 of 6
2.Food facility that utilizes multiservice eating and drinking utensils:
Assume:
1 18" X 18" three compartment sink 42 GPH
automatic dishmachine 80 GPH
hand spray pre-rinse 45 GPH
one compartment food preparation sink 5 GPH
2 hand lavatories 10 GPH (5 GPH each)
1 janitorial sink 15 GPH
197 GPH total hourly hot water demand
Since the food facility in this example uses multiservice eating and drinking
utensils, 100% of the computed hourly hot water demand must be provided.
Therefore, a water heater would be required which will recover 197 GPH.
F.To compute a BTU or KW rating for the required hourly hot water demand found in
example #1 the following formulas should be used:
Formula 1 (for gas water heaters)
BTU input = GPH X °Rise1 X 8.33 lb./ gallon of water
Thermal Efficiency2
BTU input = 54 GPH X 50°F X 8.33 lb.
.75
BTU input = 29,988
1 The average temperature of tap water varies throughout the State depending upon the
location, elevation, and time of year. In order to properly size the water heater check
with your local health agency to determine the required rise. For the purposes of these
guidelines a tap water temperature of 70° Fahrenheit will be used. Therefore, to achieve
a temperature of 120° Fahrenheit at the faucet, the required rise would be 50°.
2 The thermal efficiency for gas water heaters, unless otherwise listed by NSF
International or other nationally recognized testing laboratories, will be assumed to be
75%.
Formula 2 (for electric water heaters)
KW input = GPH X °Rise X 8.33 lb./ gallon of water
Thermal Efficiency1 X 3412 BTU/KW
KW input = 54 GPH X 50°F X 8.33 lb.
.98 X 3412 BTU/KW
KW input = 6.7
1 The thermal efficiency for electric water heaters, unless otherwise listed by NSF
International or other nationally recognized testing laboratories, will be assumed to be
98%.
Water Heater Guidelines
Page 4 of 6
Sizing tables for gas and electric water heaters are found in Appendices II and III
respectively.VII.SIZING REQUIREMENTS FOR INSTANTANEOUS WATER HEATERSA.One of the advantages of an instantaneous water heater is its ability to provide a
continuous supply of hot water. However, since the water passes through a heat
exchanger, the water must flow through the unit slowly to ensure proper heat transfer.
Therefore, the quantity, or rate, at which the hot water is delivered can be significantly
less than that provided by a storage water heater. When hot water is utilized at several
locations of the food facility at the same time the flow of hot water to each fixture can be
severely restricted. As a result of the restricted output of instantaneous water heaters,
more than one unit may be required, depending on the numbers and types of sinks and
equipment present. Due to the limitations inherent in the design of instantaneous water
heaters, some local health agencies may restrict or prohibit their usage. Check with your
local health agency prior to installing an instantaneous water heater in order to
determine their requirements.
B.Instantaneous water heaters must be sized to provide hot water of at least 120°
Fahrenheit, and at a rate of at least two gallons per minute (GPM), to each sink and
fixture that utilizes hot water. (Note: Hand lavatories must receive at least 1/2 GPM.)
The following example is provided to explain how this sizing criteria is applied:
Assume:
1 18" X 18" three compartment sink 2 GPM
2 hand lavatories 1 GPM (1/2 GPM each)
1 janitorial sink 2 GPM
5 GPM
C.In the example given above, one or more instantaneous water heaters would have to be
provided in order to supply a total of at least 5 GPM.
D.Food facilities that install an automatic warewashing machine that utilizes a large
quantity of hot water may be required to provide an instantaneous water heater
exclusively for the warewashing machine. NSF International listings or listings
established by other nationally recognized testing laboratories are used to determine the
minimum GPM hot water demand for automatic warewashing machines. VIII.REQUIREMENTS FOR BOOSTER HEATERSA.When a hot water sanitizing warewashing machine is used, a booster heater must be
provided that will raise the incoming general purpose hot water up to at least 180°
Fahrenheit for the final sanitizing rinse cycle.
B.When sizing a booster heater, the hot water demand for the warewashing final
sanitizing rinse cycle should be obtained from the NSF International listings or listings
established by other nationally recognized testing laboratories.
C.The formulas for calculating BTU or KW input listed in section VI.F. should be used
when determining the minimum required size for a booster heater.
Water Heater Guidelines
Page 5 of 6
D.When a booster heater is installed below a drainboard, it shall be installed at least six
inches above the floor and away from the wall, and in a manner that will allow
accessibility for proper cleaning and servicing.IX.RECIRCULATION PUMPSA.Where fixtures are located more than sixty feet from the water heater, a recirculation
pump must be installed, in order to ensure that water reaches the fixture at a
temperature of at least 120° Fahrenheit.
B.In some cases it may be more practical to install a separate, smaller water heater for
remote fixtures, such as for restroom handsinks.X.INSTALLATION REQUIREMENTSA.Where feasible, water heaters should be located in an area of the food facility separated
from all food and utensil handling areas.
B.The Uniform Building Code prohibits the installation of gas water heaters in restrooms or
change rooms.
C.W ater heaters shall be mounted in one of the following manners:
1.On six inch high, easily cleanable legs.
2.On a four inch high coved curb base. All openings between the water heater and
the base must be sealed in a watertight manner.
3.On a properly finished and installed wall pedestal, positioned so that it is out of the
work and traffic space.
4.In an easily accessible location above a suspended ceiling. Where a permanently
installed ladder is required to access the water heater, the ladder shall not be
installed above a food or utensil handling area.
Note: The local health agency may allow alternate installation methods when a water
heater is installed in an area separated from food and utensil handling areas, such
as in a mechanical room.
D.A common mistake with electric water heaters is the ordering and installing of a water
heater with an upper element of 4500 watts, a bottom element of 4500 watts, and a total
connected (or maximum) wattage of 4500 watts. On such a water heater only one
element is operating at any one time. Many individuals do not observe the total
connected wattage and assume that because each of the elements is 4500 watts their
water heater has an input rating of 9000 watts.
Water heater manufacturers have specific procedures for rewiring an electric water
heater so that the upper and lower elements are operating simultaneously. Some
manufacturers only permit rewiring in the factory. Field modifications will normally void
warranties and any listings that the unit comes with. Prior to acceptance of a field
modified water heater, the local health agency should ensure that the modifications
were performed according to the manufacturer's recommendations and with the
approval of the local building officials. The data plate on a field modified water heater
Water Heater Guidelines
Page 6 of 6
must be changed to reflect the total connected wattage rating with both elements
operating simultaneously.
E.When multiple water heaters are connected, they must be installed in parallel, not in
series (See Appendix IV).
July 21, 1995